The HR300 unit incorporates 2 specially developed mixed flow fans for low noise and efficiency, with up to 70% heat recovery. Effectively lowering internal relative humidity the HR300 unit controls condensation and eliminates mould growth. Designed for through the wall mounting. Fresh, pre-warmed air from outside is continually provided to the room with simultaneous extraction of stale moist air and smells. Heat is transferred via a unique plastic heat exchanger from outgoing air to the fresh air supply with no cross contamination, maintaining internal temperatures and providing a fresh environment. The unit is fully controllable for speed using a small dedicated speed controller.
Automatic ON/OFF control or switching to boost is easily achieved using sensors/timers e.g. humidistat. For summer operation the heatexchanger can be removed and replaced with a plastic divider board to provide positive cooling to rooms.
Available in three speeds: 75, 210 and 300m3/h. It is ideal for light commercial applications including function rooms, offices and classrooms.
Efficiency: The unit should retain up to 70% of the temperature differential of out going air.
Heat exchanger: Should be of a multi plate cross-flow type constructed out of a polymeric plastic with ultra sonic welded joints.
Motor: Should be a 240V 50Hz AC with sleeve bearings and greased for life. It shall operate up to an ambient temperature of 40oC and be fitted with a manual reset thermal overload protective device.
Fan: The 2-polymeric fan impellers should be of a mixed flow type, dynamically balanced mounted on a fixed stator housing.
Controls: The unit should be operated via a remote 3 Position switch, humidistat or a humidiswitch.
Back Draught Shutter: The unit should have the option back draught shutter operated via a thermal actuator set to close when unit is powered down.
Filter: Should be a washable reticulated foam type coarse filter.
Construction: The unit outer case should be a rigid ABS moulding.
The internal/external grille should be a cream coloured ABS moulding.
Complies to the following approvals/directives: LVD, EMC and CE.
Notice: Undefined variable: header_mobile_func in /home/aerovent/public_html/wp-content/themes/salient/includes/partials/footer/off-canvas-navigation.php on line 238